Information about RCCB-IID Differential 2P 40A 30mA Class ASI
This Acti9 ilD K product is a residual current circuit breaker (RCCB). It is a 2P switch with a rated current of 40A, an earth leakage sensitivity of 30mA, and an earth leakage protection class of A-SI. This product provides protection against electric shocks from direct or indirect contact and fire hazards. It disconnects electrical circuits in the event of an earth fault. Its unique Visitrip indicator reduces intervention time by displaying the faulty device with an indicator on the front. This product also has a VisiSafe window with a green strip on the lever indicating full pole opening for maintenance. This product complies with the EN/IEC 61008-1 standard. The rated making and breaking capacity (Im/I?m) is 1500A. The assigned conditional current (Inc/I?c) is 10 kA. It has electrical endurance of up to 15,000 cycles and mechanical endurance of up to 20,000 cycles. The rated operational voltage Ue is 220VAC to 240VAC.